8 RIVA PLUS MANUAL
1. General Information
The Riva Plus is a high ef ciency condensing, wall mounted gas boiler which provides central
heat. The boiler features a gas valve which modulates the energy input from 49,476 BTU/h to
116,008 BTU/h. The boiler is shipped fully assembled with the components listed on page 11.
All units are pressure and combustion tested at the factory prior to shipping.
Key Features:
Wall mountable - saving valuable oor
space.
Several ue options available
Electronic spark ignition
Safety ow switch - positioned on the
main circuit, which monitors the ow and
protects the main heat exchanger from
thermal shock should there be a lack of
water in the system.
Frost protection - contains an integral frost
protection system to prevent frost dam-
age which can occur in areas susceptible
to very cold weather conditions.
Boiler operation recognition system -
should the boiler not be used for longer
than 24 hours, it then performs a control-
led system test to ensuring the motorized
components within the boiler do not be-
come inoperable due to lack of use.
Gas valve modulation - the gas input
modulates based off central heating tem-
perature to within ± 2 ºF
Diagnostic information system equipped
with three LED diagnostic lights for quick
error assessment.
GENERAL
Height in 31.6
Width in 15.8
Depth in 13.8
Weight lb 98.1
CENTRAL HEATING
Maximum working temp. °F 185
Temp. Regulation range* °F 100-176
Maximum pressure psi 30.0
Minimum pressure psi 4.35
Max head loss (at 4.4 GPM) ft 8.3
*At the minimum useful output